Can ventilation exhaust fan be installed directly over a bathtub/ shower 2.5" x 60?"

+1 vote
Can ventilation exhaust fan be installed to MN code directly over a bathtub/shower area 30"w x 59"l x 96"h that has a 16" partition extending down  from the ceiling?
asked in Bathrooms by otto (200 points)
Share this question on your favorite network.

1 Answer

+1 vote

Hi Otto,

There are two requirements governing bathroom exhaust fan installation over the tub or shower  stall and they are both issued by the manufacturers of those devices not the building or electrical code (unless there is some exception in your particular jurisdiction).
  1. An exhaust fan must be listed for installations directly above the bathtub and / or shower stall
  2. An exhaust fan installed in such location must be installed on a GFCI protected circuit.

Let me know if you have any additional questions. Just click "comment" below.

answered by darekrudy (21,730 points)
...